Lincoln Electric 225 Welder User Manual


 
Load From WEM 2239-1
115V/230V
Dual Voltage Each Half of Total From
Receptacle Each 115V Both 115V
Duplex Duplexes
0 20* 70
1.1 KW 20* 60
3.4 KW 20* 40
5.7 KW 20* 20
8.0 KW 0 0
A-7
INSTALLATION
WELDMARK 225
A-7
115 V Duplex Receptacles
The 115V auxiliary power receptacles should only be
used with three wire grounded type plugs or approved
double insulated tools with two wire plugs.
The current rating of any plug used with the system
must be at least equal to the current load through the
associated receptacle (Refer to Tables I and II). Do not
attempt to connect power receptacles in parallel.
GND
115 V
115 V*
230 V
*Current Sensing for Automatic Idle.
(Receptacle viewed from front of Machine)
TABLE I Maximum Current Draw from 115V Duplex
Receptacles - No Welding
*NEMA 5-20P Plug required for 20Amp Draw
Load From WEM 2239-1
115V/230V
Dual Voltage Each Half of Total From
Receptacle Each 115V Both 115V
Duplex Duplex
0 15 40*
1.1 KW 15 40*
3.4 KW 15 40*
5.7 KW 15 20*
8.0 KW 0 0
TABLE II Maximum Current Draw from 115V GFCI
Duplex Receptacles - No Welding
*Maximum current draw from each 115V GFCI
Duplex is 20 amps
Motor Starting
Most 1.5 hp AC single phase motors can be started if
there is no load on the motor or other load connected
to the machine, since the full load current rating of a
1.5 hp motor is approximately 20 amperes (10
amperes for 230 volt motors). The motor may be run
at full load when plugged into only one side of the
duplex receptacle. Larger motors through 2 hp can be
run provided the receptacle rating as previously stated
is not exceeded. This may necessitate 230V operation
only.