Lincoln Electric 225 Welder User Manual


 
A-9
INSTALLATION
WELDMARK 225
A-9
Standby Power Connections
The Weldmark 225 is suitable for temporary, standby,
or emergency power using the engine manufacturers
recommended maintenance schedule.
The Weldmark 225 can be permanently installed as a
standby power unit for 230V-3 wire, single phase 35
ampere service.
(Connections must be made by a licensed electri-
cian who can determine how the 115/230V power
can be adapted to the particular installation and
comply with all applicable electrical codes.) The
following information can be used as a guide by
the electrician for most applications (refer also to
the connection diagram shown in Figure 1.)
1. Install a double pole, double throw switch between
the power company meter and the premises
disconnect.
Switch rating must be the same or greater than
the customers premises disconnect and service
overcurrent protection.
2. Take necessary steps to assure load is limited to
the capacity of the Weldmark 225 by installing a
35amp 230V double pole circuit breaker. Maximum
rated load for the 230V auxiliary is 35 amperes.
Loading above 35 amperes will reduce output
voltage below the allowable -10% of rated
voltage which may damage appliances or other
motor-driven equipment.
3. Install a 50 amp 115/230V plug (NEMA type 14-50)
to the Double Pole Circuit Breaker using No. 8,
4 conductor cable of the desired length. (The
50 amp 115/230V plug is available in the
optional plug kit.)
4. Plug this cable into the 50 amp 115/230V
receptacle on the Weldmark 225 case front.
WARNING
Auxiliary Power While Welding
It must be noted that the above auxiliary power ratings
are with no welding load. Simultaneous welding and
power loads are permitted by following Table III. The
permissible currents shown assume that current is
being drawn from either the 115V or 230V supply (not
both at the same time). Also, the Output Control is
set at 10 for maximum auxiliary power.
TABLE III
SIMULTANEOUS WELDING AND POWER
Output Selector Permissible Power Permissible Auxiliary
Setting Watts (Unity Power Current in Amperes
Factor) @ 115V -or- @ 230V
Max. Stick or Wire
Feed Setting None 0 0
175 Stick Setting 2100 18 9
125 Stick Setting 3800 32 16
90 Stick Setting 5000 42 21
70 Stick Setting 5600 48 24
50 Stick Setting 6300 54 27
NO WELDING 8000 70 35