Miller Electric M-15 Welder User Manual


 
OM-1314 Page 13
2-7. Electrical Service Guide
Input Voltage
230
Input Amperes At Rated Output
20.5
Max Recommended Standard Fuse Or Circuit Breaker Rating In Amperes
25
Min Input Conductor Size In AWG/Kcmil
14
Max Recommended Input Conductor Length In Feet (Meters)
64 (19)
Min Grounding Conductor Size In AWG/Kcmil
14
Reference: 1996 National Electrical Code (NEC) S-0092-J
2-8. Selecting A Location And Connecting Input Power
1 Rating Label
Supply correct input power.
2 Plug
3 Receptacle
Connect plug to receptacle.
4 Line Disconnect Device
See Section 2-7.
Y Special installation may be
required where gasoline or
volatile liquids are present
see NEC Article 511 or CEC
Section 20.
ssb2.2* 1/94 ST-801 504
1
18 in (457 mm) of
space for airflow
L1
L2
L1
L2
2
230 VAC, 1
Y Always connect
grounding
conductor first.
= GND/PE
4
3
Y Do not move or operate unit
where it could tip.