PARAMETERS
22
Func-
tion
Parameter
Number
Name Setting Range
Minimum
Setting
Increments
Factory Setting
Refer To
Page:
<Note9>
200
Programmed operation minute/second
selection
0 to 3
1
0
131
201
Program set 1
1 to 10
0 to 2: Rotation direction
0 to 400,
9999:Frequency
0 to 99.59: Time
1
0.1Hz
Minute or second
0
9999
0
131
211
Program set 2
11 to 20
0 to 2: Rotation direction
0 to 400,
9999:Frequency
0 to 99.59: Time
1
0.1Hz
Minute or second
0
9999
0
131
221
Program set 3
21 to 30
0 to 2: Rotation direction
0 to 400,
9999:Frequency
0 to 99.59: Time
1
0.1Hz
Minute or second
0
9999
0
131
Programmed operation
231
Timer setting
0 to 99.59
0
131
232
Multi-speed setting (speed 8)
0 to 400Hz, 9999
0.01Hz
9999
135
233
Multi-speed setting (speed 9)
0 to 400Hz, 9999
0.01Hz
9999
135
234
Multi-speed setting (speed 10)
0 to 400Hz, 9999
0.01Hz
9999
135
235
Multi-speed setting (speed 11)
0 to 400Hz, 9999
0.01Hz
9999
135
236
Multi-speed setting (speed 12)
0 to 400Hz, 9999
0.01Hz
9999
135
237
Multi-speed setting (speed 13)
0 to 400Hz, 9999
0.01Hz
9999
135
238
Multi-speed setting (speed 14)
0 to 400Hz, 9999
0.01Hz
9999
135
Multi-speed operation
239
Multi-speed setting (speed 15)
0 to 400Hz, 9999
0.01Hz
9999
135
240
Soft-PWM setting
0, 1
1
1
135
Sub functions
244
Cooling fan operation selection
0, 1
1
0
135
Stop selection
function
250
Stop selection
0 to 100 sec, 9999
0.1 sec
9999
135
Sub
functions
251
Start holding time
0 to 10 sec, 9999
0.1 sec
9999
136
261
Power failure stop selection
0, 1
1
0
137
262
Subtracted frequency at deceleration
start
0 to 20Hz
0.01Hz
3Hz
137
263
Subtraction starting frequency
0 to 120Hz, 9999
0.01Hz
60Hz<50Hz>
137
264
Power-failure deceleration time 1
0 to 3600/
0 to 360 sec
0.1 sec/
0.01 sec
5 sec
137
265
Power-failure deceleration time 2
0 to 3600/
0 to 360 sec, 9999
0.1 sec/
0.01 sec
9999
137
Power failure stop function
266
Power-failure deceleration time switch-
over frequency
0 to 400Hz
0.01Hz
60Hz
137
Selection
function
270
Stop-on-contact/load torque high-speed
frequency control selection
0, 1, 2, 3
1
0
139
271
High-speed setting maximum current
0 to 200%
0.1%
50%
140
272
Mid-speed setting minimum current
0 to 200%
0.1%
100%
140
273
Current averaging range
0 to 400Hz, 9999
0.01Hz
9999
140
High-speed
frequency
control
274
Current averaging filter constant
1 to 4000
1
16
140
275
Stop-on-contact exciting current low-
speed multiplying factor (Note 5)
0 to 1000%, 9999
1%
9999
143
Stop on
contact
276
Stop-on-contact PWM carrier frequency
(Note 5)
0, 1, 2, 9999
1
9999
143