MRV Communications AE182FCAKA Sander User Manual


 
30
Supplementary refrigerant
The refrigerant supplementation shall be as specified in the installation instructions
attached with the outdoor unit. The added refrigerant shall be R22.
The adding procedure shall be aided with a measuring meter
for a specified amount of supplemented refrigerant
Requirement
Overfilling or underfilling of refrigerant will cause compressor
fault. The amount of the added refrigerant shall be as specified
in the instructions.
Connection of refrigerant pipe
The connection of indoor unit pipes must use double spanners.
The installing torque shall be as given in the following table.
Double-spanner
operation
Connecting pipe
O.D.(mm)
ÿ6.35
ÿ9.52
ÿ12.70
ÿ15.88
Installing torque
(N-m)
11.8 (1.2kgf-m)
24.5 (2.5kgf-m)
49.0 (5.0 kgf-m)
78.4 (8.0 kgf-m)
Increased installing
torque (N-m)
13.7 (1.4 kgf-m)
29.4 (3.0 kgf-m)
53.9 (5.5 kgf-m)
98.0 (10.0 kgf-m)
Conduct flared connection work to
connect all refrigerant pipes.
Pipe cutting and expanding
If the pipe is too long or the flare is damaged,
it needs to be cut or expanded.
Pipe expander
Pipe expansion dimensions as follows:
6.35 mm (1/4
"
) 0.8 ~ 1.5
9.52 mm (3/8
"
) 1.0 ~ 1.8
12.7 mm (1/2
"
) 1.2 ~ 2.0
15.88 mm (5/8
"
) 1.4 ~2.2
Pipe diameter ÿ Size A (mm)
A
Allowable pipe length and drop
These parameters differ according to the outdoor unit. See the instruction manual attached
with the outdoor unit for details.
Pipe material and size
Pipe material
Model
Phosphorus deoxidized copper seamless pipe (TP
2
M) for air conditioner
Pipe size
(mm)
AE072FCAKA
AE092FCAKA
Gas side
ÿ9.52
Liquid side
ÿ6.35
AE122FCAKA
AE142FCAKA
ÿ12.70
ÿ6.35
Refrigerant piping
Installation Procedure
AE182FCAKA
AE212FCAKA
AE242FCAKA
ÿ15.88
ÿ9.52
1. Pipe cutting 2. Removing burrs
3.Insertion nut 4. Pipe expansion
Slope Damage Bur Partial Overlong
Correct
Incorrect