MRV Communications AE182FCAKA Sander User Manual


 
35
Timer indicator
Flashing times
Indoor unit malfunction
Flashing once The liquid tube temperature sensor is abnormal
Flashing twice The gas tube temperature sensor is abnormal
Flashing 3 times The environment temperature sensor is abnormal
Flashing 4 times The communication with outdoor unit is abnormal
Flashing 5 times The ommunication with the electronic expansion valve control board is abnormal
Flashing 6 times
The communication between indoor 846 and communication chip is abnormal
Flashing 8 times PMV strong electricity board is abnormal
Flashing 10 times Indoor unit PG fan motor is abnormal
Flashing 11 times Indoor unit water overflow or float switch is abnormal
Flashing 12 times Indoor unit EEPROM data is abnormal
Flashing 13 times Indoor unit is overload
Flashing 14 times The communication between indoor unit and wire remote controller is abnormal
Operation indicator
flashing times
Outdoor unit Trouble contents
Flashing once Outdoor unit defrost temp. sensor is abnormal
Flashing twice Outdoor unit environment temp. sensor is abnormal
Flashing 3 times ction temperature sensor is abnormal
Flashing 4 times Outdoor unit discharging temperature sensor is abnormal
Flashing 5 times Outdoor unit evapor ating temperature sensor is abnormal
Flashing 6 times Outdoor unit AC over-current protection
Flashing 7 times Outdoor unit DC voltage is insufficient protection
Flashing 9 times IPM protection
Flashing 10 times Outdoor unit EEPROM is abnormal
Flashing 11 times Compressor discharging temperature overheat protection
The communication between the 857&communication chip is abnormal
Flashing 13 times Outdoor unit high pressure protection
Flashing 14 times
High pressure sensor PD is abnormal
Flashing 15 times Low pressure sensor PS is abnormal
Flashing 12 times
Remote controller Timer and Operation indicator malfunction code
When the unit running, Timer indicator flash stand for indoor unit malfunction
operation indicator flashing stand for outdoor unit malfunction
1. Indoor unit malfunction
2.Outdoor unit malfunction
Malfunction