Adjust the LCD contrast for best viewing. A setting of 1 is lower contrast, 5 is higher.
In general, select lower contrast if the display is in warmer ambient surroundings.
Set the decimal to the best resolution for your application. The display will auto-
matically scale down to this restriction. Select *****., ****.*, ***.** **.*** or *.****
OFF provides the most instantaneous response to process changes. Select
LOW (4 sec) or HIGH (8 sec) averaging if your process experiences frequent or
extreme fluctuations.
Adjust the minimum and maximum current output. The display value represents
the precise current output. Adjustment limits:
• 3.80 mA < 4.00 mA > 5.00 mA
• 19.00 mA < 20.00 mA > 21.00 ma
Use this setting to match the system output to any external device.
Select ºC or ºF
Set the percent change in Conductivity caused by a 1ºC change in temperature.
May be from 0.00 to 10.00.
Active HIGH: This setting is used to turn a device (pump, valve) ON at the
setpoint.
Active LOW: This setting is used to turn a device OFF at the setpoint.
Press UP and DOWN keys to manually order any output current value from 3.6
mA to 21.00 mA to test the output loop.
Press UP and DOWN keys to manually toggle the Open Collector output state.
Contrast:
3>
Cond Decimal:
****.* >
Averaging
Off >
Loop Adjust:
4.00 mA >
Loop Adjust:
20.00 mA >
Temp Display:
ºC>
Temperature
Comp %: 2.00 >
Output Active:
Low >
Test Loop:
>
Test Output:
>
CDTX-90-1 Options Menu
Display
(Factory settings shown)
Description