Omega CNiS8DV Stud Sensor User Manual


 
37
ENTER OUTPUT 1 MENU:
Press
a
1) Press
a
, if necessary, until
CNFG
prompt appears.
Press
d
2) Display advances to
INPT
Input Menu.
Press
a
3) Press
a
, if necessary, until display advances to
OUT1
Output
1 Menu.
Press
d
4) Display advances to
SELF
Self Submenu.
SELF SUBMENU:
The Self Option allows the output of the instrument to be controlled manually
from the front panel.
Press
d
5) Display flashes the current setting of Self,
ENBL
Enabled or
DSBL
Disabled.
Press
b
6) Press the
b
button to select between Enable and Disable.
Press
d
7) If Self
ENBL
Enabled was selected, display shows
STRD
stored message momentarily and then advances to the next
menu (Output 1 setting is completed).
On the Run Mode display shows MXX.X The output is now
under the direct control of the operator and can be adjusted in
the Run Mode (M00.0 to M99.9), by pressing the
b
and
c
buttons, where M calls for manual (Self) control. For example,
setting of M50.0 of an analog output of 0 to 10 Vdc would
produce roughly 5 Vdc at the output.
8) If Self
DSBL
Disabled was selected, display shows
STRD
stored message momentarily and then advances to
o
o
LO
Minimum/Percent Low Submenu of Output 1 Menu.
There is a shorter way to Enable or Disable SELF Mode. From
a Run Mode press
d
and then press
a
. SELF Mode is Enabled
now. Press
b
or
c
to display MXX.X To Disable SELF press
d
and then press
a
. Display goes to the Run Mode. SELF Mode
is Disabled now.
MINIMUM/PERCENT LOW SUBMENU:
Specify in percent, the minimum value (0000) for control output. If the output is
analog proportional (Current or Voltage), then the minimum voltage or current, in
percent, is specified. If the output is time proportional (Relay, SSR or Pulse),
then the minimum duty-cycle, in percent, is specified.
Press
d
9) Display flashes 1st digit of previous “Percent Low” setting.
Press
b
&
c
10) Use
b
and
c
buttons to enter a new value for “Percent Low”.
Press
d
11) Display shows
STRD
stored message momentarily and then
advances to
o
o
HI
Maximum/Percent High Submenu.