Xantrex Technology 1000 Battery Charger User Manual


 
1–18 975-0395-01-01
This guide for use by qualified installers only
13. Insert the Line and Neutral wires into the corresponding terminals.
14. Tighten the wire attachment screws to a torque of 1.3–1.8 lbf-ft
(1.76–2.44 Nm). Leave some wiring slack inside the wiring
compartment.
15. Secure the AC cable by adjusting the strain-relief clamps.
If you do not plan to proceed with “Step 5: Connecting AC Output to
an Existing AC Circuit” on page 1–19, follow the succeeding substep.
16. Install the GFCI back into the front panel of the unit.
Alternatively, if you do not reinstall the GFCI, make sure that you cap
the exposed wires and install a blanking plate to cover the space
vacated by the GFCI.
FreedomHF_IC_01-Installation.fm Page 18 Monday, December 24, 2007 9:47 AM