14
F13 SET DISCHARGE FLOOR
DEFAULT = 100% RANGE = 50%–100% STEP = 5%
When this option is activated, you may set a discharge floor for each battery bank.
When the discharge floor is set to 50%, the Time Remaining display reports time remaining
until the battery reaches the 50% discharged level. You may set the discharge floor from
50% to 100% in 5% increments. When the Settable Discharge Floor is 100%, time remaining
to 100% discharge is displayed. You may set a discharge floor for each battery. The settable
floor is applied to the battery selected (BAT1 or BAT2) at the time you enter this function.
You may wish to set a higher discharge floor, such as 50%, for an engine starting bank and
a deeper floor, such as 75%, for a deep-cycling house bank.
F14 - ACTIVE TEMPERATURE COMPENSATION ON, OFF
DEFAULT = OFF RANGE = OFF, ON
When this function is ON, the Link 2000/Link 2000-R uses the actual battery
temperature reported from the Freedom Inverter/Charger through the temperature probe.
If the unit Inverter/Charger does not report a valid temperature reading, the Link 2000 will
use the battery temperature declared by F03 (Default: 70 °F) to set charging voltages.
Remember: charging voltages are controlled by battery type and temperature settings.
F15 - SPECIAL FUNCTION FOR DIAGNOSTIC USE.
DEFAULT ON = INVERTER CONTROL
OFF = ASCII OUTPUT
CAUTION!! LEAVE THIS FUNCTION ON. TURNING IT OFF DISABLES
COMMUNICATION. TO BE USED FOR SERVICE DIAGNOSTIC PURPOSES
ONLY.
SUMMARY OF SOFTWARE DEFAULTS
Function Name Default Options
F01 Averaging Period 0 4, 16, 32 minutes
** F02 Battery Type Lead Acid Gel cell , AGM
** F03 View or set ambient 70 °F See text
temperature
F04 View Ah or kWh OFF (Ah) ON (kWh)
F05 Alternative Energy mode Off Solar cell (see text)
F06 Peukert's Exponent Auto See text
F07 Temp Coefficient 0.5 0.1 to 0.9
** F08 Puekert's Exponent 1.25 1.00 to 1.50 (see text)
F09 % remaining time display Off (Ah mode) On (% remaining)
F10 Alternator Current limit 100 amps 30 to 220 amps, off
F11 Battery #2 used for control On (Yes) Off
F12 Backlighting intensity 130 0 to 240
F13 Settable discharge floor 100% 50% to 100%
F14 Active Temp Compensation Off On
F15 Manufacturer Reserved On Do not change
** Item that should be confirmed or changed at installation to ensure proper operation