7
SETUP
The LINK 2000 has been set up with default values chosen to work with a typical
system. Normally the only values that must be changed are:
1) Battery capacity (page 9) 3) Battery type (liquid or gel) (F02 page 11).
2) Ambient Temperature (F03 page 11) 4) Peukert's exponent (F08 page 13).
The SETUP BUTTON is used to access the functions in small blue text below each
button's primary function. It is also used for certain advanced functions described later.
To set up a value or function:
1) Select the battery to be set up by pressing Battery #1 or #2, (or Invert, or Charge, when
setting up Idle Mode or Pwr Share).
2) Hold down the SETUP BUTTON until the green LED flashes at one-second intervals.
3) Release the SETUP BUTTON and press and hold the function to be set up. The LED
of the function being set up will also begin to flash at one-second intervals. The present value
of the function will appear in the display.
4) After three seconds, with the button pressed, the display will begin scrolling. When the
desired value appears, release the button. If you continue to hold down the button, the
display will increment to the end of its range, roll over to its minimum value, and continue
to scroll. You may also "bump" a value by repeatedly pressing the button.
You may set up additional values, or functions, as long as the SETUP LED continues
to flash. When the SETUP LED stops flashing, all values that were changed during the setup
routine will be stored in nonvolatile memory.
SUMMARY OF FACTORY DEFAULT VALUES
INVERTER/CHARGER CONTROL
Standby = 4 watts (5 watts in Series 458 units)
Power Sharing = 30 amps ("OFF" for Freedom 25)
MONITORING FUNCTIONS
Charged Voltage = 13.2 volts for 12 volt systems
= 26.4 volts for 24 volt systems
Charged Current % = 2% (of battery capacity)
Battery Capacity = 200 Ah
CEF (Charge Efficiency Factor)= 87% for Liquid Acid
= 90% for other cell types
Ambient Temp. = 70 °F
Type = #0 Liquid
Peukert's Exponent= 1.25
I4.35I4.35
I4.35I4.35
I4.35