Anderson Manufacturing 8000 602 050 Rev. B Welding System User Manual


 
- 20 -
4. Enter the bin command to set a binary transfer mode
5. Enter the following command :
put SeriaLAN.lm update.lm
The first parameter SeriaLAN.lm is the provided file name. Also specify the path if
needed (D:\firmware\SeriaLAN.lm).
The other parameter is the destination file name for the SeriaLAN : it must be
update.lm.
6. Wait for the end of the transfer : SeriaLAN restarts after a few seconds. You can then
complete the FTP session (close or quit command).
D:\firmware>ftp 192.168.1.135
Connect at 192.168.1.135.
220 SeriaLAN FTP server (Version 1.13) ready.
User (192.168.1.135:(none)) :
230 User logged in.
ftp> bin
200 Type set to I.
ftp> put SeriaLAN.lm update.lm
200 PORT command successful.
150 BINARY data connection.
226 Transfer complete.
ftp : 879832 octets sent in 5.88 seconds at 149.76 Kb/sec.
ftp> quit
D:\firmware>
Proceed again with the unit configuration in case of new parameters.
It is usually required to update both units of a link : you should then update the remote
SeriaLAN first.