Elektra Beckum Cool 401 Air Compressor User Manual


 
19
11.02
Part 4 Operation
4.6.1 Change modes
4.6.1.1 P01
4.6.1.2 P02
4.6.1.3 P03
4.6.1.4 P04
4.6.1.5 P05
4.6.1.6 P06
4.6.1.7 P07
4.6.1.8 P08
4.6.1.9 P09
4.6.1.10 P10
!
Activation pressure dew point-summer set value (fac-
tory setting: pressure dew point 7 °C).
Acknowledgement of failures (see 5.1)
Acknowledgement maintenance interval (see 5.1)
Change of pressure dew point-normal set value by serv-
ice.
Change of pressure dew point-summer set value by serv-
ice.
Change of station time of condensate draining time
(optimization of condensate draining)
At normal operation conditions the condensate volume
per condensate draining time corresponds to the values
mentioned below.
Type of CA-dryer Condensate volume
405 AP, 406AP: 40cm³ - 60cm³
407 AP: 12cm³ - 18cm³
Attention!
- at greater amount of condensate per condensate
draining time the factor P06 must be lowered.
- at smaller amount of condensate per condensate
draining time the factor P06 must be raised.
P06 Minimum: Factor 1
P06 factory setting: Factor 16
P06 Maximum: Factor 33
Setting possibility of the pressure dew point failure limit
value (factory setting 18 °C).
Change °C / °F.
Activation solenoid valve condensate draining.
Activation automatic operation.