Code Function name L300P Setting range
Initial data
-FE/-FU/-FR
N o t e
A061 1
st
frequency upper limiter 0.00, 1
st
frequency lower limiter-maximum frequency(Hz) 0.00
A261 2
nd
frequency upper limiter 0.00, 2
nd
frequency lower limiter-2
nd
setting maximum
frequency(Hz)
0.00
A062 1
st
frequency lower limiter 0.00, start frequency-maximum frequency(Hz) 0.00
A262 2
nd
frequency lower limiter 0.00, start frequency-2
nd
setting maximum frequency(Hz) 0.00
A063 Jump frequency1 0.00-99.99/100.0-400.0(Hz) 0.00
A064 Jump frequency Width 1 0.00-10.00(Hz) 0.50
A065 Jump frequency2 0.00-99.99/100.0-400.0(Hz) 0.00
A066 Jump frequency Width 2 0.00-10.00(Hz) 0.50
A067 Jump frequency3 0.00-99.99/100.0-400.0(Hz) 0.00
A068 Jump frequency Width 3 0.00-10.00(Hz) 0.50
A069 Acceleration stop frequency 0.00-99.99/100.0-400.0(Hz) 0.00
A070 Acceleration stop time 0.00-60.0(s) 0.0
A071 PID selection 00(invalid)/01(valid) 00
A072 PID-P gain 0.2-5.0 1.0
A073 PID-I gain 0.0-3600.(s) 1.0
A074 PID-D gain 0.00-100.0(s) 0.00
A075 PID scale 0.01-99.99 1.00
A076 PID feedback selection 00(feedback : OI)/01(feedback : O) 00
A081 AVR selection 00(ON always)/01(OFF always)/02(OFF on decelerating) 00/00/02
A082 Motor voltage selection 200/215/220/230/240, 380/400/415/440/460/480
(230/400)
(230/460)
(200/400)
A085 Operation mode selection 00(normal operation)/01(energy-saving operation) 00
A086
Energy-saving response-
accuracy adjustment
0.0-100.0 50.0
A092 Acceleration time2 0.01-99.99/100.0-999.9/1000.-3600.(s) 15.00
A292 2
nd
acceleration time2 0.01-99.99/100.0-999.9/1000.-3600.(s) 15.00
A093 Deceleration time2 0.01-99.99/100.0-999.9/1000.-3600.(s) 15.00
A293 2
nd
deceleration time2 0.01-99.99/100.0-999.9/1000.-3600.(s) 15.00
A094 2
nd
stage adjustable selection 00(change with 2CH terminal)/01(change with setting) 00
A294
2
nd
stage adjustable
selection(2
nd
motor)
00(change with 2CH terminal)/01(change with setting) 00
A095 2
nd
acceleration frequency 0.00-99.99/100.0-400.0(Hz) 0.00
A295
2
nd
acceleration
frequency(2
nd
motor)
0.00-99.99/100.0-400.0(Hz) 0.00
A096 2
nd
deceleration frequency 0.00-99.99/100.0-400.0(Hz) 0.00
A296
2
nd
deceleration frequency
(2
nd
motor)
0.00-99.99/100.0-400.0(Hz) 0.00
A097 Acceleration pattern selection 00(straight line)/01(S-curve)/02(U-curve)/03(reverse U-curve) 00
A098 Deceleration pattern selection 00(straight line)/01(S-curve)/02(U-curve)/03(reverse U-curve) 00
A101 OI start 0.00-99.99/100.0-400.0(Hz) 0.00
A102 OI end 0.00-99.99/100.0-400.0(Hz) 0.00
A103 OI start rate 0.-100. ( %) 20.
A104 OI end rate 0.-100. ( %) 100.
A105 OI start selection 00(external start frequency)/01(0Hz) 01
A111 O2 start -400.--100./-99.9-0.00-99.9/100.-400.(Hz) 0.00
A112 O2 end -400.--100./-99.9-0.00-99.9/100.-400.(Hz) 0.00
A113 O2 start rate -100. - 100. (%) -100.
A114 O2 end rate -100. - 100. (%) 100.
A131 Acceleration curve constant 01(small swelling)-10(large swelling) 02
A132 Deceleration curve constant 01(small swelling-10(large swelling) 02
b001 Retry selection
00(trip)/01(0Hz start)/02(start after equal frequency)/
03(trip after equaling frequency and deceleration stop)
00
b002
Allowable under-voltage
power failure time
0.3-1.0(s) 1.0
b003 Retry wait time 0.3-100.(s) 1.0
b004
Instantaneous power-
failure/under-voltage trip
during stop
00(invalid/01(valid)/
02(invalid during stop and deceleration by stop command)
00
b005
Instantaneous power-
failure/under-voltage
retry time selection
00(16 times)/01(free) 00
b006 Open-phase selection 00(invalid)/01(valid) 00
b007 Frequency setting to match 0.00-99.99/100.0-400.0(Hz) 0.00
b012 Electronic thermal level 0.2*constant current-1.20*constant current(A)
Rated
Current of
inverter
b212
Electronic thermal level
(2
nd
motor)
0.2*constant current-1.20*constant current(A)
Rated
Current of
inverter
b013
Electronic thermal
characteristic selection
00/(reduced characteristic)01(constant torque characteristic)/
02(free setting)
01/01/00
b213
Electronic thermal
characteristic selection
(2
nd
motor)
00/(reduced characteristic)01(constant torque characteristic)/
02(free setting)
01/01/00
b015
Free electronic thermal
frequency 1
0.-400.(Hz) 0.
b016
Free electronic thermal
current 1
0.0-1000.(A) 0.0
b017
Free electronic thermal
frequency 2
0.-400.(Hz) 0.
b018
Free electronic thermal
current 2
0.0-1000. (A) 0.0
b019
Free electronic thermal
frequency 3
0.-400.(Hz) 0.
b020
Free electronic thermal
current 3
0.0-1000.(A) 0.0
Upper and lower
limiter / jump
frequency
PID control
External frequency
adjustment
AVR
Operation mode/ adjustable function
Accel
Decel
Instantaneous power failure
restart