Controls and Indicators
16
5.8 AC INPUT INDICATOR LED (GREEN)
The AC Input indicator LED is illuminated when utility power is
available and within the input specifications.
5.9 OUTPUT VOLTAGE SELECTION
The Output Voltage is user configurable and is designed to allow
selecting or changing the desired output voltage to match the utility
via the Liebert GXT2U Configuration Program provided with the
UPS. The settings to choose from are 100, 110, 115, 120, and 127 VAC
output. The factory default setting is 120 VAC.
!
CAUTION
Never change the voltage settings while the UPS is ON and
powering connected loads.
NOTE
Setting output voltage to 100 VAC will cause the UPS unit to
be derated (500/700/1000 VA to 90%, 1500/2000/3000 VA to
80% of the VA and Watt ratings listed in
11.0 - Specifications).