13.0 BATTERY RUN TIMES
Load% 500VA 700VA 1000VA 1500VA 2000VA 3000VA
Internal
Battery
(minutes)
10% 494 248 191 144 56 91
20% 181 115 87 53 33 46
30% 107 79 48 38 26 30
40% 83 58 34 28 19 21
50% 66 44 25 20 14 16
60% 53 35 19 15 12 11
70% 44 29 16 12 10 9
80% 36 24 13 10 8 8
90% 31 20 12 8 7 7
100% 28 17 11 7 6 5
Internal
Battery
+ 1 External
Battery
Cabinet
(minutes)
10% 1976 992 764 576 168 364
20% 726 460 348 212 99 184
30% 431 316 192 152 78 120
40% 332 232 136 112 57 84
50% 267 176 100 80 42 64
60% 210 140 76 60 36 44
70% 178 116 64 48 30 36
80% 150 96 52 40 24 32
90% 132 80 48 32 21 28
100% 115 68 44 28 18 20
Internal
Battery
+ 2 External
Battery
Cabinets
(minutes)
10% 3953 1984 1528 1152 392 728
20% 1453 920 696 424 231 368
30% 862 632 384 304 182 240
40% 665 464 272 224 133 168
50% 534 352 200 160 98 128
60% 421 280 152 120 84 88
70% 356 232 128 96 70 72
80% 300 192 104 80 56 64
90% 265 160 96 64 49 56
100% 231 136 88 56 42 40
Internal
Battery
+ 3 External
Battery
Cabinets
(minutes)
10% 5929 2976 2292 1728 560 1092
20% 2179 1380 1044 636 330 552
30% 1293 948 576 456 260 360
40% 998 696 408 336 190 252
50% 801 528 300 240 140 192
60% 632 420 228 180 120 132
70% 534 348 192 144 100 108
80% 450 288 156 120 80 96
90% 398 240 144 96 70 84
100% 346 204 132 84 60 60
Internal
Battery
+ 4 External
Battery
Cabinets
(minutes)
10% 7906 3968 3056 2304 840 1456
20% 2906 1840 1392 848 495 736
30% 1725 1264 768 608 390 480
40% 1331 928 544 448 285 336
50% 1068 704 400 320 210 256
60% 843 560 304 240 180 176
70% 712 464 256 192 150 144
80% 600 384 208 160 120 128
90% 525 320 192 128 105 112
100% 462 272 176 112 90 80
Note: Approximate discharge times are in minutes and at 77°F (25°C) with a 100% resistive load.