Communications
21
7.3 PINS 5 & 6 - ANY-MODE SHUTDOWN
1. Pin 6 of the 9-pin communication connector is used for “Any-Mode
Shutdown” of the UPS output. This control input may be used in
special applications to disable the UPS output power—both
Inverter and Bypass.
2. The Options tab allows the behavior of the Any-Mode Shutdown
feature to be modified. When the program opens, or the REFRESH
button is pressed, the UPS setting is read by the configuration
program and displayed.
7.3.1 Auto-Enable Output
7.3.2 Pin 6 Logic
If version 1.6 (or later) is used with an earlier Liebert GXT2U model
(with an earlier UPS firmware version), the Any-Mode Shutdown fea-
tures cannot be changed.
If the configuration program is used with an earlier UPS model (with
an earlier UPS firmware version) that does not support the modifica-
tion of these settings, the Options tab will display a reminder of the
factory default settings. These cannot be changed.
!
WARNING
Note that when this option is selected and the UPS output is
disabled using Pin 6, the UPS output can turn on
automatically and without warning if the Pin 6 connection is
changed.
!
WARNING
DO NOT CHANGE THIS OPTION from the factory default
setting unless you are ready to install a normally-closed
connection between Pins 5 & 6. This connection must be
maintained to use the UPS or to use the configuration
program again, including the ability to change the UPS
setting back to the default setting using the configuration
program via a serial communication link.