Battery Cabinet Specifications
34
12.0 BATTERY CABINET SPECIFICATIONS
Model Number GXT2-48VBATT GXT2-72VBATT
Used With
UPS Model
GXT2-500RT120
GXT2-700RT120
GXT2-1000RT120
GXT2-1500RT120
GXT2-2000RT120
GXT2-3000RT120
DIMENSIONS - in. (mm)
Unit
W x D x H
3.5 x 21.5 x 17
(87 x 547 x 430)
3.5 x 24.2 x 17
(87 x 618 x 430)
Shipping
W x D x H
10.5 x 27.2 x 23
(268 x 692 x 585)
10.5 x 27.2 x 23
(268 x 692 x 585)
WEIGHT - lb. (kg)
Unit 65.0 (29.5) 93.6 (42.5)
Shipping 71.1 (32.3) 102.5 (46.5)
BATTERY PARAMETERS
Type Valve-regulated, nonspillable, lead acid
Qty x V x Rating 2 x 4 x 12V x 7.0 or 7.2 AH 2 x 6 x 12V x 9.0 AH
Battery Mfg / Part #
China Storage Battery /
CSB 1270 F2
Panasonic / UP-VW1245P1
Yuasa / REW 45-12
Backup Time See 13.0 - Battery Run Times
ENVIRONMENTAL
Operating Temp +32°F to +104°F (0°C to +40°C)
Storage Temp +5°F to +122°F (-15°C to +50°C)
Relative Humidity 0% to 95%, non-condensing
Operating Elevation Up to 10,000 ft. (3000m) at 104°F (40°C) without derating
Storage Elevation 50,000 ft. (15,000 m) maximum
AGENCY
Safety UL 1778, c-UL Listed
RFI/EMI FCC Part 15, Subpart B, Class A
Transportation ISTA Procedure 1A