Oneida Air Systems 10 HP Dust Collector User Manual


 
IX. Fan / Blower - Maintenance
The Fan / Blower has a TEFC - totally enclosed fan cooled motor that can be placed outside.
The fan housing is adjustable by 22 1/2 degree increments - outlet can be oriented by adjusting bolt
hole locations between the scroll and the bracket assembly. Fan blowers come as clockwise up blast
from Oneida Air Systems.
13
Item
Dimensions
(Inches)
Dimensions
(mm)
ABDFGHLMNRSTVW
17 1/5 12 5/8 10 1/8 14 1/2 12 1/4 34 1/8 11 9 1/2 22 6 5/8
18 5/18
8 7/8 8 9 1/2
445 321 257 368 311 867 279 241 559 168 465 225 203 241
A high pressure blower requires a certain amount of resistance which will prevent motor over
amperage.
Make sure power source matches wire voltage configurations.
Check set screw and key in fan wheel, make sure fan wheel is secure, fan blower should not
vibrate.
REMINDER: Check Motor and Fan Lubrication Schedule.
Maintenance of Fan / Blower
1.) Electrical -
Failure to follow instructions and safe electrical procedures could result in serious injury or death.
Disconnect all power and discharge all capacitors before servicing. Install and ground per local and
national codes. Consult qualified personnel with questions or if repairs are required.
Electrical Connections
A) All wiring, fusing, and grounding must comply with National Electrical Codes and local codes.
B) To determine proper rotation and voltage connections, refer to the wire diagram section of this
manual.
C) Use the proper size of line current protection and motor controls as required by the National
Electrical Code and local codes. Recommended use is 125% of full load amps as shown on the
nameplate for motors with 40 degrees Celsius ambient and a service factor over 1.0. Recommended
use is 115% of full load amps as shown on the nameplate for all other motors. Do not use protection
with larger capacities than recommended. Three phase motors must have all three phases protected.
O.A.S. 2007
c
10 HP Pulley Drive Owners Manual
WARNING: Rotating Fan Blades.
Keep Objects Clear of Inlet and Outlet.
DANGER!
Do not open until the power
supply has been locked off and
the shaft has stopped rotating.
Failure to do this can result in
serious injury.