10 HP Pulley Drive Owners Manual
22
Open access cover on the overload, then set
theoverloadamperagedialtomatchtheFLA
amperage of your motor. The FLA value can
be found on your motor nameplate.
Be sure you have the proper voltage available for your Starters Power & Control
Circuit (Control circuit controls Contactor Coil in Starter). Coil voltage is/can be
independent from the line voltage that runs your motor. Customers may desire an
alternative Contactor Coil voltage to connect a Starter to a low voltage control circuit.
Most OAS Starters are shipped with 240v coils.
Plug the Start/Stop Push-Button Assembly into keyed receptacle. (As shown below.)
Run power to the starter and from the starter to your motor. See the manufacturer
instructions for more details.
The Power Circuit connected to the Starter should be fed from a dedicated circuit
breaker or disconnect with fuses. Dont connect any branch circuits to the Mag Starter
Power Circuit. The overcurrent protection (circuit breaker or fuse*) for the Starter
Power Circuit is to be sized per Article 430.32 of the NEC.
*Use time delay fuses rated for motor circuits.