Xantrex Technology 815-2524-02 Battery Charger User Manual


 
975-0697-01-01 25
Installing the Inverter/Charger
This guide for use by qualified personnel only.
Connecting AC Input Wires
Figure 6 shows the wiring compartment, which contains a
grounding bus (used to wire the AC input and output ground wires)
and a terminal block (used to wire the AC input and AC output
connections).
When making the AC input and AC output connections, observe the
correct color code for the appropriate AC wire, as described in
Table 1 on page 12.
To make the AC input connections:
1. Locate the wiring compartment cover panel and remove the
four screws.
2. Remove the cover panel from the unit to access the wiring
compartment.
3. Remove one of the AC knockouts from the front or side of the
unit. Do not leave the knockout inside the wiring compartment.
4. Install a strain-relief clamp in the AC knockout.
5. Run the AC wiring through the strain-relief clamp.
6. Strip approximately 50 mm off the jacket from the AC cable
and separate the wires.
Figure 6 AC Wiring Compartment
NCORRECT BATTER
Y POLARITY WILL CAUSE DAMAGE TO
WIRING BOX COVER MUST BE IN PLACE DURING
OPERATION TO REDUCE RISK OF INJURY TO PERSONS.
30A
CHARGER
AC INPUT
30A
INVERTER
AC INPUT
AC
IN
AC
OUT
AC GROUNDS
(BEHIND COVER)
To ground bus
EQUIPMENT DAMAGE
The terminal block is split into INPUT and OUTPUT sections. Damage
may occur if the unit is wired incorrectly.
Do not remove or loosen factory installed wiring.
Failure to follow these instructions can damage the unit and/or
damage other equipment.