Xantrex Technology 10 Battery Charger User Manual


 
Operation
3–16 975-0251-01-01
Battery Charger Voltage Settings
** When set for gel cells, the equalize mode is disabled.
Table 3-5
Battery Charger Voltage Settings
Battery Type and
Temperature
Acceptance Voltage/
Max Time Float Voltage Equalize Voltage
12-volt wet cell
warm temperature
14.0 / 1 hour 13.1 15.8
12-volt wet cell
cool temperature
14.4 / 1 hour 13.5 16.3
12-volt gel cell
warm temperature
13.8 / 3 hours 13.3 14.1**
12-volt gel cell
cool temperature
14.1 / 3 hours 13.6 14.1**
24-volt wet cell
warm temperature
28.0 / 1 hour 26.2 31.6
24-volt wet cell
cool temperature
28.8 / 1 hour 27.0 32.6
24-volt gel cell
warm temperature
27.6 / 3 hours 26.6 27.6
24-volt gel cell
cool temperature
28.2 / 3 hours 27.2 28.2