A SERVICE OF

logo

PART 7: SECTION 2.1
GASEOUS SYSTEM COMPONENTS
14 July 2008
Product Name Description System pressure (bar) LPCB Ref. No.
01-16653-0002/0102 Pressure Relief Device 200
01-16653-0003/0103 Pressure Relief Device 300
ARGONITE Pressure Monitoring Devices
Product Name Description System pressure (bar) LPCB Ref. No.
01-7221-0300 Manifold Pressure Gauge ½
150, 200 & 300 bar 594a/15
03-5713-0000 Discharge Pressure Switch Operating pressure 90 bar
01-7171-1150 Contact Gauge Unit 150
01-7171-1200 Contact Gauge Unit 200
01-7171-1300 Contact Gauge Unit 300
ARGONITE Discharge Nozzles
Product Name Description Orifice size (mm) System pressure (bar) LPCB Ref. No.
01-3465-X200 (11) ½" Nozzle Assembly
3-10 60 594a/05
01-3465-X300 (11) ¾" Nozzle Assembly 7-14 60
01-3465-X400 (11) 1.0" Nozzle Assembly 10-18 60
01-3465-X500 (11) 1½" Nozzle Assembly 15-26 60
11
Where X can be 1 for BSP or 2 for NPT connections
ARGONITE Container Valves
Product Name Description System pressure (bar) LPCB Ref. No.
01-6471-0150 Pneumatic Argonite Valve 150 594a/10
01-6471-0200 Pneumatic Argonite Valve 200
01-6471-0300 Pneumatic Argonite Valve 300
ARGONITE Release Valves
Product Name Description System pressure (bar) LPCB Ref. No.
01-7172-1150 Release Unit 150 594a/11
01-7172-1200 Release Unit 200
01-7172-1300 Release Unit 300
01-7173-1150 Release Unit 150
01-7173-1200 Release Unit 200
01-7173-1300 Release Unit 300
Kidde Fire Protection Services Limited
Station Road, High Bentham, Lancaster LA2 7NA UK
Tel: +44 (0)1524 264000 Fax: +44 (0)1524 264180
E-mail: info@kfp.co.uk Website: www.kfp.co.uk
KIDDE200 RANGE OF FM200 FIXED FIRE FIGHTING COMPONENTS
a) This range of equipment is suitable for storage temperatures from -2C to +5C and is approved for use with HFC
227ea (FM200) & Nitrogen.
b) This range of equipment is approved for use in conjunction with the Kidde200 Design Manual that also relates to
HFC 227ea (FM200).
c) System pressure is specified at 25 bar @ 20°C and max service pressure of 34.5 bar @ 5C.