PART 7: SECTION 2.2
GASEOUS SYSTEMS
38 July 2008
Fireater
Burlingham House, Hewett Road, Gapton Hall Industrial Estate, Great Yarmouth, Norfolk NR31 0NN UK
Tel: +44 (0)1493 417600 • Fax: +44 (0)1493 417700
Sapphire™
Product Name Risk Design
Concentration
Comments LPCB Ref.
No.
Fireater
Sapphire™
Class A Standard (Solid fires e.g.
paper, wood, plastics)
6.3% Design concentration includes 30%
safety factor
587Cb/01
Class A Cables (Solid fire risks
including cables)
6.1% Confirmation that minimum safety
factor is adequate
Class B (Liquid fires e.g. heptane) 6.4% Design concentration includes 30%
safety factor
Design concentration Class A Standard and Class B = Extinguishing concentration x safety factor (minimum 1.3).
Design concentration Class A Cables System test concentration. Where this value is lower than the Class A Standard value, the
Class A Standard value should be used for design purposes.
Design concentrations are as tested to LPS 1230 in BRE Test Report Number 208832 v2.
Extinguishing concentrations are as tested in BRE Test Report Number 208831 (ISO 14520-1 tests)
This system uses:
Design, Installation, Maintenance and User Manual: Fireater Novec
TM
1230 Total Flooding Systems (Engineered & Pre-
engineered) Design Manual Reference 14a-06F Issue 2
Software Programme: TSPNovec 1230 FlowCalc TSP 3.60
a) This system is suitable for storage in environmental conditions from -20° to +50°.
b) System pressure is specified as 25 bar @ 20°C
Ginge Kerr Danmark A/S
111 Stamholmen, DK-2650 Hvidovre, Denmark
Tel: +45 36 77 11 31 • Fax: +45 36 77 22 31
E-mail: ginge@ginge-kerr.dk • Website: www.ginge-kerr.com
Certificate No: 594b to ISO14529-1 and LPS 1230
Ginge Kerr Danmark 300 bar Argonite Fixed Gaseous Fire Extinguishing System
Product
Name
Risk Design
Concentration
Comments LPCB Ref.
No.
Ginge-Kerr
Argonite
Class A Standard (Solid fires e.g.
paper, wood, plastics)
40.1% Design concentration includes 30%
safety factor
594b/01
Class A Cables (Solid fire risks
including cables)
47.6% Confirmation that minimum safety
factor is adequate.
Class B (Liquid Fires e.g. heptane) 47.1% Design concentration includes 30%
safety factor
Design concentration Class A Standard and Class B = Extinguishing concentration x safety factor (minimum 1.3).
Design concentrations Class A Cables System test concentration - where this is lower than the Class A Standard value, the Class A
Standard value should be used for design purposes.
Design concentrations are as tested to LPS 1230 in BRE Test Report Number 206880.
Extinguishment concentrations are as tested in BRE Test Report Number 206879 & 216485 (ISO 14520-1 tests)
This system uses:
Design, Installation, Maintenance and User Manual: General Manual - Argonite System, MA-01-9006-0100,
Revision 9 dated 2 April 2003.
Software Programme : Ginge-Kerr Danmark A/S Argonite Program,
VdS-Version 4.6a (1998) SNR AN2700.
a) This system is suitable for storage in environmental conditions from -20° to +55°.
b) System pressure is specified as 150 bar, 200 bar and 300 bar @ 15°C.