SECTION 2.2: PART 7
GASEOUS SYSTEMS
July 2008 41
Certificate No: 855c
Nitin ‘Nitin1230’ 25 bar FK 5-1-12 Gaseous Fire Suppression System
Product
Name
Risk Design
Concentration
Comments LPCB Ref.
No.
Nitin1230 Class A Standard (Solid fires e.g.
paper, wood, plastics
5.3% Design concentration includes 30%
safety factor
855c/02
Class A Cables (Solid fires risks
including cables)
- System not LPS1230 approved for risks
including cables
Class B (Liquid Fires e.g.heptane) 6.5% Design concentration includes 30%
safety factor
Design concentration Class A Standard and Class B = Extinguishing concentration x safety factor (minimum 1.3).
Design concentrations are as tested to LPS 1230 in BRE Test Report Number 231870
Extinguishing concentrations are as tested in BRE Test Report Number 231870 (ISO 14520-1 tests).
This system uses:
Design Manual: ‘Nitin Fire Novec227 Manual’ – Issue 11 ‘Feb08’
Software Program: VdS Schadenverhutung calculation package version 7.2 .
This system is suitable for storage and environmental conditions from -20º to 50º.
System pressure is specified as 25 bar at 20ºC.
Tyco Fire and Integrated Solutions (the trading company for Tyco Fire and Integrated
Solutions (UK) Limited and Tyco Fire and Integrated Solutions (Ireland) Limited)
Tyco Park, Grimshaw Lane, Newton Heath, Manchester M40 2WL UK
Tel: +44 (0)161 205 2321 • Fax: +44 (0)161 455 4459
E-mail: wfs.manchester@tycoint.com • Website: www.tycofis.com
Certificate No: 014b to LPS 1230
Product Name Risk Design
Concentration
Comments LPCB Ref.
No.
Wormald Ansul
INERGEN
Class A Standard) Solid fires e.g.
paper, wood, plastics)
43% Design concentration includes 30%
safety factor
014b/01
Class A Cables (Solid fire risks
including cables)
47.8%- Confirmation that minimum safety
factor is adequate
Class B (Liquid fires e.g. heptane) 46.7% Design concentration includes 30%
safety factor
Design concentration Class A Standard and Class B = Extinguishing concentration x safety factor (minimum 1.3).
Design concentration Class A Cables System test concentration. Where this value is lower than the Class A Standard value, the
Class A Standard value should be used for design purposes.
Design concentrations are as tested to LPS 1230 in BRE Test Report Number 206885.
Extinguishing concentrations are as tested in BRE Test Report Number 206884 (ISO 14520-1 tests)
This system uses:
Design, Installation, Maintenance and User Manual:
INERGEN 200 bar manual, Issue July 2002, including Appendix B '200 bar
INERGEN L.P.I. systems,
Software Programme:
C.A.P Version 14.04
a) This system is suitable for storage in environmental conditions from -20° to +50°C.
b) System pressure is specified as 200 bar @ 20°C
c) If this fixed gaseous fire extinguishing system is used with existing pipework (so called drop-in systems) it is the responsibility of
the installing company to ensure that:
- all pipework can withstand system pressures and will be safe during operation;
- all pipework meets the requirements of the gas system manufacturers design manual; and
- all applicable legislation is complied with.