![](https://pdfstore-manualsonline.prod.a.ki/pdfasset/f/ca/fca34441-0a55-4ed1-bcb3-4d3e4efe8e9f/fca34441-0a55-4ed1-bcb3-4d3e4efe8e9f-bg84.png)
Chapter 4 Parameters|
Revision July 2008, EG03, SW V1.06 4-81
3.5 Address list:
The contents of available addresses are shown as below:
Content Address Function
AC drive
Parameters
GGnnH GG means parameter group, nn means parameter number,
for example, the address of Pr 04-01 is 0401H. Refer to
chapter 5 for the function of each parameter. When reading
parameter by command code 03H, only one parameter can
be read for one time.
Bit 0-1 00B: Disabled
01B: Stop
10B: Run
11B: Jog + Run
Bit 2-3 Reserved
Bit 4-5 00B: Disabled
01B: FWD command
10B: REV command
11B: Direction change command
Bit 6-7 00B: 1st step acce/decel speed
01B: 2nd step acce/decel speed
10B: 3rd step acce/decel speed
11B: 4th step acce/decel speed
Bit 8-11 0000B: Master speed
0001B: 1st step speed
0010B: 2nd step speed
0011B: 3rd step speed
0100B: 4th step speed
0101B: 5th step speed
0110B: 6th step speed
0111B: 7th step speed
1000B: 8th step speed
1001B: 9th step speed
1010B: 10th step speed
1011B: 11th step speed
1100B: 12th step speed
1101B: 13th step speed
1110B: 14th step speed
1111B: 15th step speed
Bit 12 Select Bit6~11 function
2000H
Bit 13-15 Reserved
2001H Freq. command
Bit 0 1: EF (external fault) on
Bit 1 1: Reset
Command
Write only
2002H
Bit 2 0: BB OFF
1: BB ON