![](https://pdfstore-manualsonline.prod.a.ki/pdfasset/f/ca/fca34441-0a55-4ed1-bcb3-4d3e4efe8e9f/fca34441-0a55-4ed1-bcb3-4d3e4efe8e9f-bg42.png)
Chapter 4 Parameters|
Revision July 2008, EG03, SW V1.06 4-15
Parameter Functions Settings
Factory
Setting
Customer
08-11 Operation Frequency
Inhibition 1 UP
0.00~160.00 Hz 0.00
08-12 Operation Frequency
Inhibition
1 DOWN
0.00~160.00 Hz 0.00
08-13 Operation Frequency
Inhibition 2 UP
0.00~160.00 Hz 0.00
08-14 Operation Frequency
Inhibition
2 DOWN
0.00~160.00 Hz 0.00
08-15 Operation Frequency
Inhibition 3 UP
0.00~160.00 Hz 0.00
08-16 Operation Frequency
Inhibition
3 DOWN
0.00~160.00 Hz 0.00
08-17 Automatic Energy-
saving
00: Energy-saving operation disabled
01: Energy-saving operation enabled
00
08-18 Automatic Voltage
Regulation (AVR)
00: AVR function enabled
01: AVR function disabled
02: AVR function disabled for deceleration
00
08-19 Software Setting of the
Braking Level (the
action level of the
braking resistor)
740V~820VDC
00:Disabled
760
08-20 Vibration
Compensation Factor
00~1000 00
Group 9 Communication Parameters
Parameter Functions Settings
Factory
Setting
Customer
09-00 Communication
Address
01-254
00:Disabled
01
09-01 Transmission Speed
(Baud Rate)
00: Baud rate 4800
01: Baud rate 9600
02: Baud rate 19200
03: Baud rate 38400
01
09-02 Transmission Fault
Treatment
00: Warn and keep operating
01: Warn and RAMP to stop
02: Warn and COAST to stop
03: No warning and no display
03
09-03 Over Time Detection
during Transmission
00: Disabled
01: Enabled
00
09-04 Communication
Format
00: 7-bit for ASCII
01: 8-bit for ASCII
02: 8-bit for RTU
00