Exide S47-0079 Battery Charger User Manual


 
13
2.1.12 Programming
To enter programming mode, press and hold the EDIT button and while holding it, press the INFO button. The
display shows a message describing the current parameter followed by the parameter‘s value. While in
programming mode, the buttons have the following functions:
STOP: Exit programming mode and save all parameters
=: Shift position of parameter being edited
EDIT: Change value of current position of parameter being edited
INFO: Change parameter to edit
Some of the parameters may be locked out in the programming mode. If a parameter is locked, the parameter is
displayed along with the current value and a lock is displayed on the left side of the display. The parameter can not
be changed. Refer to jumper settings section for information on locking out parameters. The following parameters
are available for editing:
PARAMETER MESSAGE RANGE NOTES LOCK
BS BATTERY AH SIZE 100-2200AH
VR BATTERY VOLTAGE 12-999V
SR SHUNT RATING 0-600A A setting of 0 enables current sensor operation
AS AUTO START MODE 0-2
0: Manual Start
1: Auto-Start
2: Auto Start (restart on AC power)
CR CABLE RESISTANCE 0-25m
SA START A/100AH 5.0-50.0 A/100AH
TP 80% TRIP POINT 2.35-2.45 V/C
FA FINISH A/100AH 0.1-10.0 A/100AH
FV FINISH VOLTAGE 2.50-3.00 V/C
CV CUTOFF VOLTAGE 2.50-3.00 V/C Exceeding this voltage terminates the charge immediately.
ST 80% TIMEOUT 0:00-24:00
Exceeding this time results in an F1 if F1 is enabled and ends
normally if F1 is disabled. (see N1 parameter)
FT CHARGE TIMEOUT 0:00-24:00
Exceeding this time results in an F7 if F7 is enabled and ends
normally if F7 is disabled. (see N7 parameter)
MP MAX POWER RATING 0.1-25.0 kW *DO NOT EXCEED RATING OF CHARGER
CF CHARGE FACTOR 0-150%
Maximum return based on battery AH size. Setting this to 0 disables
the charge factor.
DS DELAY START TIME 0:00-24:00
CT COOL DOWN TIME 0:00-24:00
CU DVDT PERIODS 0-15
Each period is 5 minutes. Setting this to 0 causes the charge to
terminate when the trip point is reached. (opportunity charge)
EM EQUALIZE MODE 0-1
0: Equalize disabled
1: Normal equalize
EI EQUALIZE A/100AH 0.1-10.0 A/100AH
ET EQUALIZE TIME 0:00-24:00
EC EQUALIZE CYCLES 0-30 Setting this to 0 disables automatic equalize.
N1 F1 FAULT DISABLE 0-1 0: Enabled, 1: Disabled
N3 F3 FAULT DISABLE 0-1 0: Enabled, 1: Disabled
N4 F4 FAULT DISABLE 0-1 0: Enabled, 1: Disabled
N6 F6 FAULT DISABLE 0-1 0: Enabled, 1: Disabled
N7 F7 FAULT DISABLE 0-1 0: Enabled, 1: Disabled
AR REFRESH TIME 00:00-72:00 Setting this to 0:00 disables automatic refresh.