4-11. Electrical Service Guide
Input Voltage
220 230 380 440 460 575
Input Amperes At Rated Output
178 170 103 89 85 68
Max Recommended Standard Fuse Rating In Amperes
1
Time-Delay
2
200 200 125 110 100 80
Normal Operating
3
250 250 150 125 125 100
Min Input Conductor Size In AWG
4
3/0 2/0 2 3 3 4
Max Recommended Input Conductor Length In Feet (Meters)
230
(70)
214
(65)
349
(106)
389
(118)
424
(129)
554
(169)
Min Grounding Conductor Size In AWG
4
4 4 6 6 6 8
Reference: 2005 National Electrical Code (NEC)
1 Consult factory for circuit breaker applications.
2 “Time-Delay” fuses are UL class “RK5” .
3 “Normal Operating” (general purpose - no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and
above).
4 Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table
310.16. If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable requirements.