Outback Power Systems Outback Power Systems Battery Charger User Manual


 
Installation & Programming Manual FX & VFX “E” Series Inverte r/Charge r Sy ste m Copyright 2003 OutBack Power Systems, Inc.
19009 62
nd
Ave NE, Arlington WA 98223 USA
Page 48 Rev 7.0 07/02/04 Tel 360 435 6030 Fax 360 435 6019
MATE - ADVANCED / GEN
The GEN (generator) category of the advanced menu section allows for adjustment of the AC input voltage window and time delays to
match the characteristics of the AC source if that AC source is a generator. This setting can be found in the SETUP/FX/INPUT menu.
All OutBack Power System FX’s other than the “Grid-Tie” FX’s have a default of GEN (generator) as the AC source.
ADV-----------------
choose product:
FX MATE
ADV/FX/PAGE1--------
choose category:
ADV INV CHGR PG2
ADV/FX/PAGE2--------
choose category:
PG1 GRID GEN PG3
ADV/FX/GEN-------P00
ac input 00.5 min
connect delay
DOWN INC DEC PORT
ADV/FX/GEN-------P00
ac2/gen 208 vac
lower limit
DOWN INC DEC PORT
ADV/FX/GEN-------P00
ac2/gen 270 vac
upper limit
DOWN INC DEC PORT
ADV/FX/GEN-------P00
ac2/gen 24.0 aac
input limit
DOWN INC DEC PORT
ADV/FX/GEN-------P00
ac2/gen 60 cycles
transfer delay
DOWN INC DEC PORT
ADV/FX/GEN-------P00
ac2/gen
support
DOWN OFF ON PORT
ADV/FX/GEN----------
GEN programming
completed
TOP ADV MAIN
Once the password has been correctly entered, the ADV - CHOOSE PRODUCT is displayed.
Selecting
<FX> allows adjustment of the FX’s advanced programming.
Selecting
<PG2> advances the user to the second page of the advanced menu.
Selecting
<GEN> allows adjustment of the AC input set points and operation.
The
AC INPUT CONNECT DELAY set point adjusts the time period of when the FX sees an
acceptable AC source to when it connects the AC loads to that source. This is useful to allow a
generator to warm up. This setting has a range between 0.2 minutes to 15 minutes in 0.1 minute
increments.
The
AC2/GEN LOWER LIMIT set point allows adjustment of the minimum voltage that the AC
source is allowed to be in order for the FX to connect to that source. The FX will back off the
charger if the AC source is at this lower limit. If the AC source falls below this limit, the FX will
disconnect from the AC source until it is above this value. This setting has a range between 80
vac and 220 vac in 2 vac increments.
The
AC2/GEN UPPER LIMIT set point allows adjustment of the maximum voltage that the AC
source is allowed to be in order for the FX to connect to that source. If the AC source exceeds this
value, the FX will disconnect from the AC source until it is below this value. This setting has a
range between 250 vac and 300 vac in 2 vac increments.
The
AC2/GEN INPUT LIMIT sets the maximum amount of current the FX allows to be drawn from
the AC source. When the AC input current limit is reached, the power draw of the battery charger
is backed off to prevent overloading the AC source. If the AC loads exceed this limit, the FX will
give a warning and start blinking the red “ERROR” LED. This setting has a range between 2.5 aac
and 30.0 aac in 0.5 aac increments.
The
AC2/GEN TRANSFER DELAY is the amount of time that the AC input will remain connected
to the AC source when the AC input voltage drops below the AC1/GEN
LOWER LIMIT setting.
Once the AC voltage has risen above the AC1/GEN
LOWER LIMIT setting for the AC INPUT
CONNECT DELAY time period the AC source will be reconnected.
This setting has a range
between 0 cycles and 240cycles in 1 cycle increments.
The
AC2/GEN SUPPORT setting allows the FX to assist the generator for very large AC loads or if
the generator’s continuous power is less than the continuous power of the FX and the loads are
drawing more power than the generator can give. For this feature to work properly, the generator