Trane RTUB 207-224 Air Compressor User Manual


 
11
Installation
condensation coils must be
protected from side winds when
their speed exceeds 16 km/h.
Position the unit above the average
height of snow observed in the
region where it is installed. Never
install temporary or permanent
objects (tarp or roof) over the unit,
because recycling of hot air would
reduce the capacity of the
condensation coils. Discharged air
from the fans must not be
obstructed. It is prohibited to install
ducts for the fan discharge air (even
short ones). This is because the fans
supplied on standard units do not
generate any additional static
pressure.
Clearances
Provide enough space around the
unit to allow the installation and
maintenance personnel unrestricted
access to all service points. Refer to
Figure 5 and Table 4 for unit
Figure 5: Unit Dimensions and
Recommended Minimum
Clearances - RTCA
Figure 6: Unit Dimensions and
Recommended Minimum
Clearances - RTUB
A
C
D
B
A
C
D
B
Table 4 - Unit Dimensions and Recommended Minimum Clearances (mm)
Length Width Height A B C D
RTCA 108/109/111/208/209/211 2870 2285 1630 1000 1000 1000 1000
RTCA 113/213 4610 2285 1630 1000 1000 1000 1000
RTCA 115/116/215/216 5450 2285 1630 1000 1000 1000 1000
RTUB 207/208 2880 890 1789 950 800 1800 500
RTUB 210/211/212/214/216/217 4150 890 1832 950 800 2750 500
RTUB 218/220 4150 890 1932 950 800 2750 500
RTUB 222/224 4150 890 2041 950 800 2750 500
dimensions and recommended
clearances. Unobstructed flow of
condenser air is essential to maintain
chiller capacity and operating
efficiency.
Note for RTCA: When determining
unit placement, give careful
consideration to ensuring a sufficient
flow of air across the condenser
heat-transfer surface.
RLC-SVX03A-E4