PROBLEM: AC product will not operate, red FAULT light ON.
Possible Cause
AC product(s) connected are rated at more
than 240 watts; overload shutdown has
occurred.
AC Product is rated less than 240 watts;
high starting surge has caused overload
shutdown.
Battery is discharged (alarm is sounding).
Jazz 300 has overheated due to poor
ventilation and has caused over temperature
shutdown.
Input voltage is greater than 15.0 volts.
Suggested Remedy
Use product with a power rating less than
240 watts (or 120 volts/2.0 amps).
Product exceeds inverters surge capability.
Use a product with starting surge power
within the Jazz 300s capability.
Recharge battery.
Switch Jazz 300 OFF and allow to cool for
15 minutes. Clear blocked fan or remove
objects covering unit. Locate unit to a cooler
environment. Reduce load if continuous
operation is required. Restart.
Verify charging system is properly regulated
and battery is 12 volts nominal.