Hobart Welding Products HP-70 Welder User Manual


 
. A complete Parts List is available at www.MillerWelds.com
OM-244 013 Page 14
4-8. Electrical Service Guide
Failure to follow these electrical service guide recommendations could create an electric shock or fire hazard. These recommenda-
tions are for a dedicated branch circuit sized for the rated output and duty cycle of the welding power source.
NOTICE ï INCORRECT INPUT POWER can damage this welding power source. This welding power source requires a CONTINUOUS supply of
input power at rated frequency(+10%) and voltage (+10%). Phase to ground voltage shall not exceed +10% of rated input voltage. Do not use a genera-
tor with automatic idle device (that idles engine when no load is sensed) to supply input power to this welding power source.
60 Hz Single
Phase
Input Voltage (V) 208 230
Input Amperes (A) At Rated Output 33 30
Max Recommended Standard Fuse Rating In Amperes
1
Time-Delay Fuses
2
40 35
Normal Operating Fuses
3
50 45
Min Input Conductor Size In AWG
4
3 10
Max Recommended Input Conductor Length In Feet (Meters)
80
(24)
98
(30)
Min Grounding Conductor Size In AWG
4
10 10
Reference: 2008 National Electrical Code (NEC) (including article 630)
1 If a circuit breaker is used in place of a fuse, choose a circuit breaker with time-current curves comparable to the recommended fuse.
2 “Time-Delay” fuses are UL class “RK5” . See UL 248.
3 “Normal Operating” (general purpose - no intentional delay) fuses are UL class “K5” (up to and including 60 amps), and UL class “H” ( 65 amps and
above).
4 Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table
310.16. If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable requirements.
4-9. Extension Cord Data
. When calculating max. cord length, remember to include conductor length from line disconnect device to input power receptacle.
Input Voltage
Input Power
Phase
Hertz
Fuse Size Or
Circuit Breaker Rating
Conductor Size Max. Cord Length
208 V 1 60
Time-Delay
2
40 A
Normal Operating
3
50 A
10 AWG 80 ft (24 m)
230 V 1 60
Time-Delay
2
35 A
Normal Operating
3
45 A
10 AWG 98 ft (30 m)
2 “Time-Delay” fuses are UL class “RK5” .
3 “Normal Operating” (general purpose ï no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and
above).