Compact® NSF and NSJ 150 to 600 A Circuit Breakers
Section 6—Motor Circuit Protectors
© 1995–2003 Schneider Electric All Rights Reserved
20
UL 489 Recognized Component
IEC 947-2 and EN 60947-2 Ratings
p
u
s
h
t
o
tr
i
p
06153033
Compact
®
Circuit Breakers NSJ400HC NSJ600HC
Number of Poles
33
Rated Voltage (V)
AC 50/60 Hz 600 600
Rated Current (A) In
40° C
400 (100% Rated
Circuit Breaker)
600
Magnetic Trip Setting Im
2000–4000 3000–6000
Compact
®
Circuit Breakers NSF150HC NSF250HC
Number of Poles
33
Rated Insulation Voltage (V) Ui
750 750
Rated Impulse Withstand
Voltage (kV)
Uimp
88
Rated Operational Voltage (V) Ue
AC 50/60 Hz 690 690
DC 500 500
Rated Current (A) In
40° C 400 600
HC HC
Ultimate Breaking Capacity Icu
AC 50/60 Hz 220/240 V 100 100
(kA rms) 380/415 V 70 70
440 V 65 65
500 V 30 30
525 V 35 35
660/690 V 20 20
DC 250 V (1 pole) 85 85
500 V (2 poles in series) 85 85
Service Breaking Capacity Ics
(% Icu) 100% 100%
Utilization Category
AA