Schneider Electric Class 615 Power Hammer User Manual


 
Compact® NSF and NSJ 150 to 600 A Circuit Breakers
Section 9—Accessories
© 1995–2003 Schneider Electric All Rights Reserved
30
SHUNT TRIP AND UNDERVOLTAGE TRIP
A voltage release can be used to trip the circuit breaker via a control signal.
Undervoltage trip
(MN)
Trips circuit breaker when the control voltage drops below a tripping threshold
Drops out between 35% and 70% of rated voltage
Circuit breaker closing is possible only if the voltage exceeds 85% of rated voltage
Permanent type
If an overvoltage condition exists, operation of circuit breaker closing mechanism will not permit the
main contacts to touch, even momentarily
Shunt trip (MX) Trips the circuit breaker when control voltage rises above 70% of its rated voltage
Impulse type 20 ms or maintained control signals
AC shunt trips can be operated at 55% of their rated voltage, making them suitable for ground-fault
protection when combined with a Class I ground-fault sensing element
Operation The circuit breaker must be reset locally after being tripped by shunt trip or undervoltage trip
(MN or MX)
MN or MX tripping has priority over manual (or motor operator) closing; in the presence of a
standing trip order such an action does not result in any closing, even temporarily, of the main
contacts
Endurance: 50% of the rated mechanical endurance of the circuit breaker for Compact
®
NSF150–
NSJ600 circuit breakers
Installation and
Connection
Accessories are common to NSF and NSJ circuit breakers and are located within the circuit breaker
behind front accessory cover
Each terminal may be connected by one #18–#14 AWG (1.0–2.5 mm
2
) stranded copper wire
06153102
Electrical Characteristics
AC DC
Rated Voltage (V)
24, 48, 110–130, 208–277, 380–480, 525, 600 12, 24, 30, 48, 60, 125, 250
Consumption
Pickup (MX) < 10 VA < 5 W
Seal-in (MN) < 5 VA < 5 W
Clearing Time (ms)
< 50 < 50