Compact® NSF and NSJ 150 to 600 A Circuit Breakers
Section 13—Supplementary Technical Information
© 1995–2003 Schneider Electric All Rights Reserved
72
Test Sequences
Sequence Category of Devices Tests
1–General Characteristics All Circuit Breakers
Trip Unit Control
Dielectric Properties
Mechanical and Electrical Endurance
Overload
Dielectric Voltage Withstand
Temperature Rise
145% Calibration (3 Phases Test)
2–Breaking Capacity During Operation All Circuit Breakers
Breaking Capacity During Operation (Ot-CO-t-CO)
Dielectric Voltage Withstand
Temperature Rise
145% Calibration (3 Phases Test)
3–Ultimate Breaking Capacity (Icu)
A
B if Icu > Icw
200% Calibration (Each Pole Separately)
Ultimate Breaking Capacity (O-t-CO)
Dielectric Voltage Withstand
250% Calibration (Each Pole Separately)
4–Admissible Short Duration Current (Icw) B
200% Calibration (Each Pole Separately)
Short-time Current Withstand
Temperature Rise
Breaking Capacity at Admissible Short-time Current (O-t-CO)
Dielectric Voltage Withstand
200% Calibration (Each Pole Separately)
Combined Sequence
Icw = Ics Replaces Sequences 2
and 4
Icw = Ics = Icu Replaces
Sequences 2, 3 and 4
200% Calibration (Each Pole Separately)
Short-time Current Withstand Icw
Breaking Capacity at Ics (O-CO-CO) at Maximum Relay Temp.
Dielectric Voltage Withstand
Temperature Rise
200% Calibration (Each Pole Separately)