Crestron electronic DIN-1DIMU4 Work Light User Manual


 
Crestron DIN-1DIMU4 DIN Rail Universal Dimmer
Setup
Network Wiring
When wiring the Cresnet network, consider the following:
Use Crestron Certified Wire.
NOTE: Cresnet HP cannot be used.
Use Crestron power supplies for Crestron equipment.
Provide sufficient power to the system.
CAUTION: Insufficient power can lead to unpredictable results
or damage to the equipment. Please use the Crestron Power
Calculator to help calculate how much power is needed for the
system (
www.crestron.com/calculators).
Use of a Cresnet hub/repeater (DIN-HUB) is advised whenever the
number of Cresnet devices on a network exceeds 20 or when the
combined total length of Cresnet cable exceeds 914 meters (3000
feet).
For more details, refer to “
Check Network Wiring” which starts on page
28.
Identity Code
The Net ID of the DIN-1DIMU4 has been factory set to 86. The Net IDs
of multiple DIN-1DIMU4 devices in the same system must be unique.
Net IDs are changed on the front panel of the DIN-1DIMU4 or from a
personal computer (PC) via Crestron Toolbox™ (refer to “
Establishing
Communication
” on page 22).
To set the Net ID using the front panel:
Press the SETUP button to enter the Setup mode. The SETUP
LED illuminates.
Press the left button under the NET ID display to change the most
significant digit of the Net ID or press the right button under the
Operations & Installation Guide – DOC. 6668A DIN Rail Universal Dimmer: DIN-1DIMU4 13