Exide PAR20 Work Light User Manual


 
10
5.8 Stacking Limitations
There are recommended limits on stacked (horizontal
only) battery configurations, see Table B and consult your
layout/wiring diagram.
TABLE B
Absolyte GX Stacking Limitations for the 2-Cell Tray
GX System Non-Seismic Seismic
GX2000 6 High 6 High
GX3000 6 High 6 High
GX4000 6 High 6 High
GX5000 6 High 6 High
GX6000 6 High 6 High
3-Cell GX2000 trays provide UBC Zone 4 compliance
when stacked 4 modules high and UBC Zone 1 compli-
ance at 8 modules high.
5.9 Terminal Plates
Each system is supplied with a terminal plate assembly
for the positive and negative terminations. These should
always be used to provide proper connection to the oper-
ating equipment and cell terminals.
Any attempt to connect load cables directly to cell termi-
nal may compromise battery system performance as well
as the integrity of cell post seals.
5.10 Grounding
It is recommended that the modules or racks be ground-
ed in accordance with NEC and/or local codes. See
Appendix C for recommended procedure.
SECTION 6: UNPACKING
PACKAGED MODULES
Figure 2
6.0 General
Do not remove shipping materials if a storage period is
planned, unless charging is required per Section 4.2.
The battery modules are generally packed in groups.
Lag bolts retain the modules to the shipping pallet
together with a protective hood bolted in place. Modules
are also bolted together at the top adjacent channels.
See Figure 2.
6.1 Accessories
NOTE: Check accessory package against packing list to
assure completeness. Do not proceed with instal-
lation until all accessory parts are available.
Accessories are packed separately and will include the
following:
Layout/wiring diagram
Installation and operating instructions
Lifting straps and lifting shackles
Bottom Supports - I beams
Hardware bag for I beam installation
Hardware bag for module to module connections
Standard clear covers
Top clear covers
Clear cover mounting brackets and assembly hardware
Terminal plates
Terminal plate mounting bracket
Terminal plate hardware kit
Terminal Plate Cover and assembly hardware
Module tie plates and hardware (where required)
Lead-Tin Plated copper connectors
Hardware bag for connectors
NO-OX-ID
®
“A” * grease
Battery warning label
Battery nameplate
Cell numerals with polarity indicators
Shims (leveling)
Seismic Shims (where required)
• Alignment (drift) pins
*Registered Trademark of Sanchem Inc.
6.2 Recommended Installation Equipment
and Supplies
Fork lift, portable boom crane or A-Frame hoist
GX2000 Module Weight: 315 kg (695 lb)
GX3000 Module Weight: 447 kg (985 lb)
GX2000 3-Cell Module Weight: 478 kg (1050 lb)
— Bottom Support (I-beams) Height: 10 mm (4 in)
Chalk line
Line Cord
Torpedo level (Plastic)
Plywood straight edge 1/2” x 4” x 48”
Torque wrenches (100 in-lbs, 35 ft-lbs)
Ratchet wrench with 10, 13, 17, 19 mm and
1/2 in. sockets
Box wrenches 10, 13, 17, 19 mm sizes
Vinyl electrical tape
Paper wipers
3M Scotch Brite® scour-pads™*
Hammer drill (Floor anchoring)
* Registered trademark of 3M