10
5.8 Stacking Limitations
There are recommended limits on stacked (horizontal
only) battery configurations, see Table B and consult your
layout/wiring diagram.
TABLE B
Absolyte GX Stacking Limitations for the 2-Cell Tray
GX System Non-Seismic Seismic
GX2000 6 High 6 High
GX3000 6 High 6 High
GX4000 6 High 6 High
GX5000 6 High 6 High
GX6000 6 High 6 High
3-Cell GX2000 trays provide UBC Zone 4 compliance
when stacked 4 modules high and UBC Zone 1 compli-
ance at 8 modules high.
5.9 Terminal Plates
Each system is supplied with a terminal plate assembly
for the positive and negative terminations. These should
always be used to provide proper connection to the oper-
ating equipment and cell terminals.
Any attempt to connect load cables directly to cell termi-
nal may compromise battery system performance as well
as the integrity of cell post seals.
5.10 Grounding
It is recommended that the modules or racks be ground-
ed in accordance with NEC and/or local codes. See
Appendix C for recommended procedure.
SECTION 6: UNPACKING
PACKAGED MODULES
Figure 2
6.0 General
Do not remove shipping materials if a storage period is
planned, unless charging is required per Section 4.2.
The battery modules are generally packed in groups.
Lag bolts retain the modules to the shipping pallet
together with a protective hood bolted in place. Modules
are also bolted together at the top adjacent channels.
See Figure 2.
6.1 Accessories
NOTE: Check accessory package against packing list to
assure completeness. Do not proceed with instal-
lation until all accessory parts are available.
Accessories are packed separately and will include the
following:
• Layout/wiring diagram
• Installation and operating instructions
• Lifting straps and lifting shackles
• Bottom Supports - I beams
• Hardware bag for I beam installation
• Hardware bag for module to module connections
• Standard clear covers
• Top clear covers
• Clear cover mounting brackets and assembly hardware
• Terminal plates
• Terminal plate mounting bracket
• Terminal plate hardware kit
• Terminal Plate Cover and assembly hardware
• Module tie plates and hardware (where required)
• Lead-Tin Plated copper connectors
• Hardware bag for connectors
• NO-OX-ID
®
“A” * grease
• Battery warning label
• Battery nameplate
• Cell numerals with polarity indicators
• Shims (leveling)
• Seismic Shims (where required)
• Alignment (drift) pins
*Registered Trademark of Sanchem Inc.
6.2 Recommended Installation Equipment
and Supplies
• Fork lift, portable boom crane or A-Frame hoist
— GX2000 Module Weight: 315 kg (695 lb)
— GX3000 Module Weight: 447 kg (985 lb)
—
GX2000 3-Cell Module Weight: 478 kg (1050 lb)
— Bottom Support (I-beams) Height: 10 mm (4 in)
• Chalk line
• Line Cord
• Torpedo level (Plastic)
• Plywood straight edge 1/2” x 4” x 48”
• Torque wrenches (100 in-lbs, 35 ft-lbs)
• Ratchet wrench with 10, 13, 17, 19 mm and
1/2 in. sockets
• Box wrenches 10, 13, 17, 19 mm sizes
• Vinyl electrical tape
• Paper wipers
• 3M Scotch Brite® scour-pads™*
• Hammer drill (Floor anchoring)
* Registered trademark of 3M