Lincoln Electric SVM168-B Welder User Manual


 
RANGER® 10,000 & RANGER® 10,000 PLUS
INSTALLATION
A-11 A-11
240 Volt
60 Hz.
3-Wire
Service
P
OWER
COMPANY
M
ETER
2
40 VOLT
1
20 VOLT
1
20 VOLT
LOAD
N
NEUTRAL
BUS
GROUND
PREMISES
DISCONNECT AND
SERVICE
OVERCURRENT
PROTECTION
GND
N
4 CONDUCTOR COPPER CABLE
SEE NATIONAL ELECTRICAL CODE
FOR WIRE RECOMMENDATIONS.
240 VOLT
GROUNDED CONDUCTOR
40 AMP
240 VOLT
DOUBLE
POLE
CIRCUIT
BREAKER
DOUBLE POLE DOUBLE THROW
S
WITCH RATING TO BE THE SAME
AS OR GREATER THAN PREMISES
SERVICE OVERCURRENT
P
ROTECTION.
50 AMP, 120/240
VOLT PLUG
NEMA TYPE 14-50
50 AMP, 120/240 VOLT
RECEPTACLE
Connection of RANGER® 10,000 to premises
wiring must be done by a licensed electrician and
must comply with the National Electrical Code and
all other applicable electrical codes.
Figure A.1
CONNECTION OF RANGER® 10,000 OR RANGER® 10,000 PLUS TO PREMISES WIRING