Outback Power Systems FX 2024 T Welding System User Manual


 




























14
AC HOT OUT
Supplies the AC hot output conductors
through a 30 amp maximum AC branch
rated circuit breaker using 6 AWG wire and
connect to the AC
AC NEUTRAL OUT/AC NEUTRAL IN
Connects the AC neural input conductor to
the AC NEUTRAL IN terminal.
Connects the AC neutral output conductor
to the AC NEUTRAL OUT terminal.
Do not assume these terminals are
common in the Mobile FX.
CHASSIS GROUND
Connects both the AC input and AC output
ground conductors to the CHASSIS GROUND
and NEU/GROUND BOND terminals.
If there is only one Mobile FX in the system,
leave the copper bus (provided) installed
between the CHASSIS GROUND and NEU/
GROUND BOND terminals. If there is more
than one Mobile FX in the system, remove
the copper bus from every Slave FX.
AC HOT IN
The AC hot input conductor (black) must be
supplied through a 30 amp maximum AC
branch rated circuit breaker and connected
to the AC HOT IN.
6 AWG wire is required for the FX’s AC
transfer switch.
AC WIRING NOTES FOR THE MOBILE FX