14
AC HOT OUT
• Supplies the AC hot output conductors
through a 30 amp maximum AC branch
rated circuit breaker using 6 AWG wire and
connect to the AC
AC NEUTRAL OUT/AC NEUTRAL IN
• Connects the AC neural input conductor to
the AC NEUTRAL IN terminal.
• Connects the AC neutral output conductor
to the AC NEUTRAL OUT terminal.
• Do not assume these terminals are
common in the Mobile FX.
CHASSIS GROUND
• Connects both the AC input and AC output
ground conductors to the CHASSIS GROUND
and NEU/GROUND BOND terminals.
• If there is only one Mobile FX in the system,
leave the copper bus (provided) installed
between the CHASSIS GROUND and NEU/
GROUND BOND terminals. If there is more
than one Mobile FX in the system, remove
the copper bus from every Slave FX.
AC HOT IN
• The AC hot input conductor (black) must be
supplied through a 30 amp maximum AC
branch rated circuit breaker and connected
to the AC HOT IN.
• 6 AWG wire is required for the FX’s AC
transfer switch.
AC WIRING NOTES FOR THE MOBILE FX