Outback Power Systems FX 2024 T Welding System User Manual


 
29
APPENDIX
RATINGS
NOMINAL AC OUTPUT VOLTAGE OF AN FX SYSTEM
Single Phase 120 VAC at 60 Hz
Series Stacked 120 VAC at 60 Hz per AC output leg / 240 VAC at 60Hz between the AC output legs
Parallel Stacked 120 VAC at 60 Hz on one AC output leg
ree Phase Stacked 120 VAC at 60 Hz per AC output leg (limit three) / 208 VAC at 60 Hz between AC output legs
RECOMMENDED FX DC VOLTAGE RANGE
NOTE: The last two digits in the model number designate the nominal DC voltage. Example: FX2024MT
– 24V DC Voltage.
12V Systems 11 – 16 VDC (VDC = volts DC)
24V Systems 22 – 32 VDC
32V Systems 29 – 43 VDC
48V Systems 44 – 64 VDC
MAXIMUM DC INPUT CURRENT
NOTE: This is the maximum DC current the FX will draw from the battery when starting very large AC loads.
It is not used for sizing the DC disconnect or selecting DC cable gauge. It is used to select the minimum
reasonable battery capacity.
12V FXs 600 ADC per FX (ADC = amps DC)
24V FXs 300 ADC per FX
32V FXs 225 ADC per FX
48V FXs 150 ADC per FX