Outback Power Systems FX 2024 T Welding System User Manual


 
31
FX2012(M)T AC Max = 12 AAC (Default = 10 AAC) DC Max = 100 ADC
FX2524(M)T AC Max = 14 AAC (Default = 12 AAC) DC Max = 55 ADC
FX2532(M)T AC Max = 14 AAC (Default = 12 AAC) DC Max = 40 ADC
FX3048T AC Max = 14 AAC (Default = 12 AAC) DC Max = 35 ADC
VFX2812(M) AC Max = 16 AAC (Default = 14 AAC) DC Max = 125 ADC
VFX3524(M) AC Max = 20 AAC (Default = 18 AAC) DC Max = 85 ADC
VFX3232(M) AC Max = 20 AAC (Default = 18 AAC) DC Max = 60 ADC
VFX3648 AC Max = 20 AAC (Default = 18 AAC) DC Max = 45 ADC
AC INPUT FREQUENCY RANGE
NOTE:
If the AC input source is out of the range noted below, the FX will not connect or stay connected.
All FX Models 56 - 64 Hz
MAXIMUM AC OUTPUT CURRENT
This is the amount of surge current that the FX will quickly supply for a split second. Depending on the
size of the surge, the FX can be overloaded for a minimum time of 5 seconds to a maximum time of 30
minutes.
All 12 VDC FXs 56 AAC per FX for 1 millisecond
All Other FXs 70 AAC per FX for 1 millisecond
MAXIMUM CONTINUOUS OUTPUT POWER
An FX Series Inverter/Charger’s model number indicates its maximum continuous output power by
changing the last two digits to zeros. For instance, an FX2012MT has a maximum continuous output
power of 2000VA (volt-amps).
FX2012(M)T 2000 VA (VA = volt-Amps)
FX2024(M)T 2000 VA
FX2532(M)T 2500 VA
FX2548T 2500 VA
VFX2812(M) 2800 VA
VFX3524(M) 3500 VA
VFX3232(M) 3200 VA
VFX3648 3600 VA
MAXIMUM AND DEFAULT AC INPUT AND DC (bulk stage) OUTPUT VALUES