Outback Power Systems GS8048 Welding System User Manual


 
Operation
30 900-0020-01-00 Rev A
Gen Alert
is used as a controller for an AC generator with a remote start feature, although it has limited
functionality. (The generator recharges batteries using the inverter’s battery charger.) When the battery
voltage falls to a low set point for a settable delay, the AUX output is activated. The AUX output is used to
energize a relay. The relay contacts then activate the remote start/stop circuit on the generator. This is
illustrated in the Radian Series Inverter/Charger Installation Manual.) The AUX output will be deactivated once
the battery voltage rises to a high voltage setting for a settable delay period.
Parameters include:
Low and high DC voltage
On and off delay
Gen Alert control logic is located in the inverter. It has the advantage of functioning when the system
display is removed. However, it may not completely charge the batteries and does not have all the
advantages of the Advanced Generator Start (AGS) feature that is found in the system display. For many
users, the AGS feature may prove more useful than Gen Alert. Gen Alert, however, could be used as a literal
“Generator Alert”, a signal to the user to manually start a generator.
Fault
enables the AUX output when the inverter shuts down due to an error condition (see page 39). It can
activate a light or alarm to show that the inverter has failed. With the appropriate devices, it could send an
alarm signal through a radio, pager, or telephone dialer.
This function does not have settable parameters.
This function is not triggered by the Phase Loss error, as that error does not shut down the inverter.
Vent Fan
enables the AUX output in response to a high DC (battery) voltage set point. It can run a small fan
to ventilate the battery compartment to eliminate gases that result from battery charging. When the
voltage falls below this set point for a settable delay period, the AUX output turns off.
Parameters include:
High DC voltage
Off delay
Cool Fan
enables the AUX output when the inverter reaches a high internal temperature. It is intended to
trigger a small external fan for additional cooling. See the Warning Troubleshooting table on page 40 for a
description of the fan criteria.
This function does not have settable parameters.
DC Divert
enables the AUX output to divert excess renewable energy to a DC load, such as a resistor, a
heater, or a fuel cell. When battery voltage rises above a settable high voltage level, the AUX output is
activated after a settable delay. The AUX output controls a larger relay, which allows current to flow from the
batteries to a dedicated DC load when energized. (This is illustrated in the Radian Series Inverter/Charger
Installation Manual.) Diversion is activated by high DC voltage and is usually used to regulate battery
charging. The resistor must be sized to dissipate all of the energy from the renewable source if necessary.
Diversion will turn off following a delay when a low DC voltage setting is reached.
Parameters include:
Low and high DC voltage
On and off delay
IEEE
enables the AUX function as an alert that the utility grid does not meet IEEE parameters for the
grid-interactive function (see page 46). It can activate a light or alarm to show that the grid-interactive
function has shut down and that there may be problems with the grid. The AUX output will cycle on and off
if IEEE parameters are met and the IEEE timer is counting down.
This function does not have settable parameters.