Specifications
900-0020-01-00 Rev A 47
The acceptance ranges are selected using the system display. In the MATE3, the options are
IEEE
and
user.
The
IEEE
option allows a range of 108 – 132 Vac at 59.3 – 60.5 Hz
The
user
option does not have a fixed voltage setting. It follows the upper and lower limit settings in the
Grid AC Input Mode and Limits menu. The default is a range of 108 – 132 Vac.
Reconnection delay is 6 seconds. Sell delay is 5 minutes. These settings are not adjustable.
Firmware Revision
This manual applies to Radian series inverter/chargers with a firmware version of 001.000.xxx
or higher.
Default Settings and Ranges
Table 11 GS8048 Inverter Settings
Field Item Default Minimum Maximum
INVERTER
Hot Key Inverter Mode
Off On, Off, or Search
CHARGER
Hot Key Charger Control
On On or Off
AC Input
Hot Key AC Input Mode
Use Drop or Use
Sensitivity (see page 16 for increments)
10 0 250
Pulse Length
8 AC cycles 4 AC cycles 20 AC cycles
Search
Pulse Spacing
60 AC cycles 4 AC cycles 120 AC cycles
Input Priority Grid Grid or Gen
Grid Input AC Limit
50 Aac 5 Aac 55 Aac
Gen Input AC Limit
50 Aac 5 Aac 55 Aac
AC Input and
Current Limit
Charger AC Limit
30 Aac 0 Aac 30 Aac
Input Mode Grid Tied
Generator, Support, Grid Tied, UPS, Backup,
Mini Grid
Voltage Limit Lower
108 Vac 70 Vac 110 Vac
(Voltage Limit)Upper
132 Vac 125 Vac 140 Vac
Transfer Delay
6 AC cycles 0 AC cycles 240 AC cycles
Grid AC Input
Mode and Limits
Connect Delay
0.2 minutes 0.2 minutes 15 minutes
Input Mode Generator
Generator, Support, Grid Tied, UPS, Backup,
Mini Grid
Voltage Limit Lower
108 Vac 70 Vac 110 Vac
(Voltage Limit) Upper
140 Vac 125 Vac 140 Vac
Transfer Delay
6 AC cycles 0 AC cycles 240 AC cycles
Gen AC Input
Mode and Limits
Connect Delay
0.5 minutes 0.2 minutes 15 minutes
AC Output
Output Voltage
240 Vac 220 Vac 260 Vac
Cut-Out Voltage
42 Vdc 36 Vdc 48 Vdc
Low Battery
Cut-In Voltage
50 Vdc 40 Vdc 56 Vdc
Absorb Voltage
57.6 Vdc 52 Vdc 64 Vdc
(Absorb) Time
1.0 hours 0.0 hours 24.0 hours
Float Voltage
54.4 Vdc 48 Vdc 60 Vdc
(Float) Time
1.0 hours 0.0 hours 24.0 hours
Battery Charger
Re-Float Voltage
50 Vdc 48 Vdc 52 Vdc
Equalize Voltage
58.4 Vdc 56 Vdc 68 Vdc
Battery Equalize
(Equalize) Time
1.0 hours 0.0 hours 24.0 hours