Shindaiwa DGW310DMC Welder User Manual


 
29
Caution
The AC volt meter reads 3-P 200/200V apart from the circuit breakers position at ON or OFF
when the engine driving.
After the engine starts Refer to 7-1.Starting , operate as per the following procedures.
1 Turn the power switch off on the load.
2 Check and confirm the breakers position at OFF .
3 Select the correct frequency, designated in the loads.
4 Connect the loads to receptacle or terminals.
5 Close the terminal cover and fix it with the bolts.
6 Turn the breakers to ON .
Return -The circuit breaker has activated due to overload
Caution: Injuries
Be sure to turn the power switch to OFF on the load when returning the circuit breaker to ON again,
when the circuit breaker has activated.
When the electric supply exceeds the rated output, the breaker activates to trip in order to shut down the
circuit. Check the breakers when the load stops operation.
ELCB lamp is to turn OFF in the case of overload shutdown. When the lamp keeps ON, refer to 5-6.
ELCB and Grounding .
When any breaker has activated, return the circuit breaker per the followings procedure.
1 Turn OFF all the power switches on the loads.
2 Once push down the breaker lever to OFF , push up the lever to ON .
Caution
Take care for overload, referring to 9-2 Output Limitation
The breaker activates when having used AC output in the selector switch at ECO position. In the
case stop using AC supply and return the breaker as above.
MC
DMC
Breaker
3
-
P/1
-
P 200/220V
Output Terminals
Rece
pta
c
l
e
1-P 100/110V
Output Terminals
Terminal
Cover
Breaker
Receptacle
1-P/3-P
200/220V
Output
Terminals
1-P 100/110V
Output Terminals
Output
Terminal
Cover