Section 3 - Specifications Installing In-Sight™ 4000 Series Vision Sensors
32
3.2.3 Discrete Outputs
Table 3-6: Discrete Output Specifications
SPECIFICATION DESCRIPTION
Voltage 28V maximum through external load.
200mA maximum sink current.
OFF state leakage current 200µA maximum
External load resistance 120 to 10K Ohms
Current
Each line rated at a maximum 200mA, protected against over-current, short circuit, and transients from
switching inductive loads. High current inductive loads require external protection diode.
Both of the built-in discrete outputs (pins 4 and 5) on the In-Sight 4000 are NPN (pull-
down) lines. The external load should be connected between the output and the
positive supply voltage (<28V). The outputs pull down to 0V when ON, which causes
current to flow through the load. When the outputs are OFF, no current flows through
the load.
Figure 3-2: Discrete Output Connection Example 1
To connect to an NPN-compatible PLC input, connect Output 0 or Output 1 directly to
the PLC input. When enabled, the output pulls down the PLC input to 0V.
Figure 3-3: Discrete Output Connection Example 2