Hitachi L300IP Welding System User Manual


 
9
Error Codes
The L300P series inverters will trip on over-current, over-voltage, and
under-voltage to protect the inverter. The motor output turns OFF, allow-
ing the motor to free-run to a stop. Press the Stop/Reset key to reset the
inverter and clear the error.
Basic Error Codes
Error
Code
Name Probable Cause(s)
E01
Over current event while at
constant speed
Inverter output was short-circuited
Motor shaft is locked
Load is too heavy
A dual-voltage motor is wired
incorrectly
Note: The L300P will over current trip
at nominally 200% of rated current
E02
Over current event during
deceleration
E03
Over current event during
acceleration
E04
Over current event for other
conditions
DC braking power(A054) set too high
Current transformer / noise error
E05
Overload protection Motor overload is detected by the
electronic thermal function
E06
Braking resistor overload Regenerative braking resistor exceeds
the usage time or usage ratio
E07
Over voltage
protection
DC bus voltage exceeds a threshold,
due to regenerative energy from motor
E08
EEPROM error Built-in EEPROM memory experi-
enced noise, high temperature, etc.
E09
Under-voltage error DC bus voltage decreased enough to
cause a control circuit fault
E10
CT error
(current transformer)
High electrical noise near inverter
A fault occurred in the built-in CT
E11
CPU error Built-in CPU had internal error
E12
External trip [EXT] input signal detected
E13
USP (Unattended Start
Protection)
When (USP) was enabled, an error
occurred when power was applied while
a Run signal was present
E14
Ground fault A ground fault was detected between
the inverter output and the motor. This
feature protects the inverter, and does
not protect humans.
E15
Input over-voltage Input voltage was higher than the
specified value, 60 sec. after powerup
E16
Instantaneous power failure Input power removal > 15ms or
> B002... inverter restarts on Run cmd