24
“H” Group: Motor Constants Functions
C091 Debug mode enable
• 00 Display • 01 No display
00
C101 Up/Down memory mode selection
• 00 Clear last frequency (return to F001)
• 01 Keep last freq. adjusted by UP/DWN
00
C102 Reset mode selection
• 00 Cancel trip state at input signal ON
transition, Stops inverter if in Run Mode
• 01 Cancel trip state at signal OFF transi-
tion, Stops inverter if in Run Mode
• 02 Cancel trip state at input signal ON
transition, no effect if in Run Mode
00
C103 Restart mode after reset
•00Restart at 0 Hz
• 01 Resume after frequency matching
00
Func.
Code
Name / Description
Default Value
–FE2 / –FU2 /
–FR
Set
Value
H003/
H203
Motor capacity Factory set
H004/
H204
Motor poles setting
• 2 poles • 4 poles
• 6 poles • 8 poles
4
H006/
H206
Motor stabilization constant 100.
Func.
Code
Name / Description
Default Value
–FE2 / –FU2 /
–FR
Set
Value