20
b022 Overload restriction setting Rated current x
1.20 / 1.10 /
1.20
b023 Deceleration rate at overload restriction 1.00 / 15.00 /
1.00
b024 Overload restriction operation mode (2)
• 00 Disabled
• 01 Enabled for accel and constant speed
• 02 Enabled for constant speed only
01
b025 Overload restriction setting (2) Rated current
x 1.20
b026 Deceleration rate at overload restriction (2) 1.00
b031 Software lock mode selection
• 00 Low-level access, [SFT] blocks edits
• 01 Low-level access, [SFT] blocks edits
(except F001 and Multi-speed parameters)
• 02 No access to edits
• 03 No access to edits except F001 and
Multi-speed parameters
• 10 High-level access, including b031
01
b034 Run/power on warning time 0.
b035 Rotational direction restriction
• 00 Enable for both directions
• 01 Enable for forward only
• 02 Enable for reverse only
00
b036 Reduced voltage start selection
• 00 Short
• 01, 02, 03, 04, 05 (middle)
• 06 Long
06
b037 Function code display restriction
• 00 Display all
• 01 Display only utilized functions
• 02 Display user-selected functions only
(configure with U01 to U12)
00
b080 [AM] terminal analog meter adjustment 180
b081 [FM] terminal analog meter adjustment 60
b082 Start frequency adjustment 0.50
b083 Carrier frequency setting 3.0
b084 Initialization mode (parameters or trip
history)
• 00 Trip history clear
• 01 Parameter initialization
• 02 Trip history clear and parameter initial-
ization
00
Func.
Code
Name / Description
Default Value
–FE2 / –FU2 /
–FR
Set
Value