Pin Function
A Gun Trigger
B-
C Common
D
Dual Procedure
E Common
&%+)&##*' + &%*
It is recommended that only genuine Lincoln control
cables be used at all times. Lincoln cables are specifi-
cally designed for the communication and power
needs of the Power Wave Source / Power Feed sys-
tem. The use of non-standard cables, especially in
lengths greater than 25ft(7.6m), can lead to communi-
cation problems (system shutdowns), poor motor
acceleration (poor arc starting) and low wire driving
force (wire feeding problems).
Lincoln control cables are copper 5 conductor cable in
a SO-type rubber jacket. There is one 20 gauge twist-
ed pair for network communications. This pair has an
impedance of approximately 120 ohms and a propa-
gation delay per foot of less than 2.1 nanoseconds.
There are two 12 gauge conductors that are used to
supply the 40 VDC to the network. The fifth wire is 18
gauge and is used as an electrode sense lead.
- ##&%+)&##
" Control cable only. Available in lengths of
8'(2.4m), 16'(4.9m), 25'(7.6m), 50'(15.2m) and
100'(30.5m).
A
B
C
D
E
Trigger Lead
Wire Feeder
Amphenol
Welding Gun
A
B
C
D
E
Trigger Lead
Wire Feeder
Amphenol
Welding Gun
%*+##+ &%
'&.)S$* %#. ))
'*I;F5:'AE;F;A@
ON
OFF
'A>3D;FK
(negative) - polarity
(positive) + polarity
,)
&%+)&##
&%+)&##&%%+ &%*
• All system control cables are the same.
• All control cables can be connected end to end to
extend their length.
• All system equipment must be connected to a con-
trol cable.
+KB;53>7@5:7767DA@@75F;A@
Control cable is connected from the Power Wave
Source output Amphenol receptacle to the input
Amphenol receptacle on the back of the Wire Drive.
;9;F3>A@FDA>34>7"JJ
Pin Function
A Digital I/O
B Digital I/O
C "67" voltage sense
D 40 VDC
E 40 VDC
Use a maximum of 250 feet (76.2m) of control cable
between components.